Model Inputs
{'MODEL_DIR': '/Users/dpinney/gdrive/LATERBASE/NRECA/MICROGRIDUP (MGU) ESTCP FY2020/del2.2.1K - Requirements and Specifications/microgridup mgu test system lehigh/data/projects/lehigh1mg', 'BASE_DSS': '/Users/dpinney/gdrive/LATERBASE/NRECA/MICROGRIDUP (MGU) ESTCP FY2020/del2.2.1K - Requirements and Specifications/microgridup mgu test system lehigh/testfiles/lehigh_base_1mg.dss', 'LOAD_CSV': '/Users/dpinney/gdrive/LATERBASE/NRECA/MICROGRIDUP (MGU) ESTCP FY2020/del2.2.1K - Requirements and Specifications/microgridup mgu test system lehigh/testfiles/lehigh_load.csv', 'QSTS_STEPS': 480, 'FOSSIL_BACKUP_PERCENT': 1, 'REOPT_INPUTS': {'solar': 'on', 'wind': 'off', 'battery': 'on', 'year': '2017', 'analysisYears': '25', 'discountRate': '0.083', 'energyCost': '0.12', 'demandCost': '20', 'urdbLabelSwitch': 'off', 'wholesaleCost': '0.034', 'solarCost': '1600', 'windCost': '4989', 'batteryPowerCost': '840', 'batteryCapacityCost': '420', 'batteryPowerCostReplace': '410', 'batteryCapacityCostReplace': '200', 'batteryPowerReplaceYear': '10', 'batteryCapacityReplaceYear': '10', 'dieselGenCost': '1000', 'solarMin': 0, 'windMin': 0, 'batteryPowerMin': 0, 'batteryCapacityMin': 0, 'solarMax': '10000', 'windMax': '1000', 'batteryPowerMax': '10000', 'batteryCapacityMax': '10000', 'dieselMax': '10000', 'solarExisting': 0, 'criticalLoadFactor': '1', 'outageDuration': '48', 'fuelAvailable': '150000', 'genExisting': 0, 'minGenLoading': 0, 'batteryKwExisting': 0, 'batteryKwhExisting': 0, 'windExisting': 0, 'dieselFuelCostGal': 1.5, 'dieselCO2Factor': 24.1, 'dieselOMCostKw': 35, 'dieselOMCostKwh': 0.02, 'value_of_lost_load': '100', 'solarCanCurtail': True, 'solarCanExport': True, 'dieselOnlyRunsDuringOutage': False}, 'MICROGRIDS': {'mg0': {'loads': ['634a_data_center', '634b_radar', '634c_atc_tower', '675a_hospital', '675b_residential1', '675c_residential1', '692_warehouse2', '684_command_center', '652_residential', '611_runway', '645_hangar', '646_office'], 'switch': '650632', 'gen_bus': '670', 'gen_obs_existing': ['solar_634_existing', 'solar_675_existing', 'fossil_684_existing', 'fossil_646_existing', 'battery_634_existing', 'battery_684_existing'], 'critical_load_kws': [70, 90, 10, 150, 200, 200, 400, 20, 30, 70, 0, 0]}}, 'FAULTED_LINE': '650632', 'DIESEL_SAFETY_FACTOR': False, 'OUTAGE_CSV': '/Users/dpinney/gdrive/LATERBASE/NRECA/MICROGRIDUP (MGU) ESTCP FY2020/del2.2.1K - Requirements and Specifications/microgridup mgu test system lehigh/testfiles/lehigh_random_outages.csv', 'CRITICAL_LOADS': None, 'CREATION_DATE': '2023-07-10 12:40:24', 'DESCRIPTION': ''}
User Warnings
More than one load voltage is specified on microgrid mg0. Check Oneline diagram to verify that phases and voltages of ['634a_data_center', '634b_radar', '634c_atc_tower', '675a_hospital', '675b_residential1', '675c_residential1', '692_warehouse2', '684_command_center', '652_residential', '611_runway', '645_hangar', '646_office'] are correctly supported by gen_bus 670.
Pre-existing battery battery_634_existing will not be utilized to support loads in microgrid mg0.
Pre-existing battery battery_684_existing will not be utilized to support loads in microgrid mg0.
Supporting critical loads across microgrids assumes an AMI metering system. If not currently installed, add budget for the creation of an AMI system.
Supporting critical loads across microgrids assumes the ability to remotely disconnect 3-phase loads.